120 VAC FLASHER (FL-120)

GENERAL: The flasher shall be moisture and corrosion resistant and shall be capable of dissipating heat sufficient for continuous duty.

FLASH RATE: The flasher shall have two alternately flashing circuits. Each circuit shall flash .50 seconds on and .50 seconds off.

INPUT VOLTAGE: Standard input voltage shall be 120VAC. The flasher shall operate properly for input voltages within 10% of nominal.

OUTPUT VOLTAGE AND AMPERAGE: The circuits shall be rated at 10 amps at 120VAC each (10 amps total load). A voltage drop of up to 6 volts to the output terminals shall be acceptable.

FUSE: Fuse shall be 10 amp, 250 Volt, fast-acting, cartridge-type, ¼" diameter, 1 ¼" long, UL and/or CSA approved.


TERMINALS:
Terminals shall be clearly labeled and shall be compression type screw terminals.

 


 

12 VAC FLASHER (FL-12)

GENERAL: The flasher shall be moisture and corrosion resistant and shall be capable of dissipating heat sufficient for continuous duty.

FLASH RATE: The flasher shall have two alternately flashing circuits, and one steady burn circuit. Each flashing circuit shall flash .50 seconds on and .50 seconds off.

INPUT VOLTAGE: Standard input voltage shall be 120VAC. The 120V/12V transformer shall provide 12V for the flasher and the arm lights. The flasher shall operate properly for input voltages within 10% of nominal.

OUTPUT VOLTAGE AND AMPERAGE: The output circuits shall be rated at 10 amps at 12VAC each (10 amps total load). A voltage drop of up to .5 volts to the output terminals shall be acceptable.

OVERLOAD PROTECTION: Built-in, internal overload protection with auto-reset (no fuse required).


TERMINALS:
Terminals shall be clearly labeled and shall be compression type screw terminals.